| SPD class | T |
| SPD monitoring system | LifeCheck |
| Nominal voltage (UN) | 6 V |
| Max. continuous operating voltage (d.c.) (Uc) | 6 V |
| Max. continuous operating voltage (a.c.) (Uc) | 4.2 V |
| Max. input voltage acc. to EN 60079-11 (Ui) | 4.2 V |
| Max. input current according to EN 60079-11 (Ii) | 4.8 A |
| Max. input current acc. to EN 60079-11 (without protection module only up to 60 °C) (Ii) | 4.8 A |
| D1 Lightning impulse current (10/350 µs) per line (Iimp) | 1 kA |
| C2 Total nominal discharge current (8/20 µs) (In) | 10 kA |
| C2 Nominal discharge current (8/20 µs) line-line (In) | 300 A |
| C2 Nominal discharge current (8/20 µs) per line (In) | 5 kA |
| Voltage protection level line-line for In C2 (UP) | ≤ 35 V |
| Voltage protection level line-PG for In C2 (UP) | ≤ 1800 V |
| Voltage protection level line-line at 1 kV/µs C3 (UP) | ≤ 20 V |
| Voltage protection level line-PG at 1 kV/µs C3 (Up) | ≤ 1400 V |
| Cut-off frequency line-line (fG) | 100 MHz |
| Capacitance line-line (C) | ≤ 25 nF |
| Capacitance line-PG (C) | ≤ 20 pF |
| Operating temperature range (TU) | -40 °C ... +80 °C |
| Degree of protection (with plugged-in protection module) | IP 20 |
| Pluggable into | base part |
| Earthing via | base part |
| Enclosure material | polyamide PA 6.6 |
| Colour | blue |
| Test standards | IEC 61643-21 / EN 61643-21 |
| Approvals *) | ATEX, IECEx, CCC, CSA & USA Hazloc, SIL, Inmetro, UKCA |
| SIL classification | up to SIL3 *) |
| ATEX approvals (1) | KEMA 06ATEX0274 X: II 2 (1) G Ex ia [ia Ga] IIC T6 ... T4 Gb |
| ATEX approvals (2) | KEMA 06ATEX0274 X: II 2 G Ex ib IIC T6 ... T4 Gb |
| IECEx approvals (1) ( ) | DEK 11.0078X: Ex ia [ia Ga] IIC T6 ... T4 Gb |
| IECEx approvals (2) | DEK 11.0078X: Ex ib IIC T6 ... T4 Gb |
| CSA & USA Hazloc approvals (1) | 70000011: Class I Div. 1; Class I Zone 1 |
| CSA & USA Hazloc approvals (2) | 70000011: Ex ia [ia] IIC T6 ... T4 |
| China Compulsory Certification | CCC No. 2021312304001156 |
| Inmetro approvals | TÜV 17.0697 X: Ex ib IIC T6 ... T4 Gb |
Space-saving surge arrester module with LifeCheck for protecting 1 double wire of intrinsically safe measuring circuits and RS485 bus systems. Insulation strength > 500 V wire-earth. LifeCheck detects thermal or electrical overload conditions after which the arrester must be replaced. The indication is contactless using DEHNrecord LC / SCM / MCM.