| Technical data |
| SPD class | M |
| Max. continuous operating voltage DC (UC) | 33 V |
| Nominal current at 80°C (IL) | 0.1 A |
| D1 Total lightning impulse current (10/350 µs) (Iimp) | 10 kA |
| C2 Total nominal discharge current (8/20 µs) (In) | 20 kA |
| Series resistance per line | 28.8 Ohm |
| Cut-off frequency line-PG (fG) | 1.7 MHz |
| Approvals | CSA, ATEX, IECEx, CSA & USA Hazloc, SIL |
Space-saving combined surge arrester module with LifeCheck for protecting 2 pairs of symmetrical interfaces with input diode protection circuit, current loops (TTY) and optocoupler inputs. LifeCheck detects thermal or electrical overload conditions after which the surge arrester must be replaced. The indication is contactless using DEHNrecord LC / SCM / MCM.