| General |
| SPD class | M |
| Max. continuous operating voltage DC (UC) | 180 V |
| Permissible superimposed signal voltage (Usignal) | ≤ +/- 5 V |
| Cut-off frequency line-line (Usignal, balanced 100 ohms) (fG) | 50 MHz |
| Nominal current at 80 °C (equal to max. short-circuit current) (IL) | 100 mA |
| D1 Total lightning impulse current (10/350 µs) (Iimp) | 10 kA |
| C2 Total nominal discharge current (8/20 µs) (In) | 20 kA |
| Series resistance per line | ≤ 10 ohms; typically 7.5 Ohm |
| Approvals | CSA, UL 497B, SIL |
Space-saving combination surge arrester module with actiVsense technology with RFID LifeCheck to protect 2 double wires with the same or different operating voltage of symmetrical interfaces with galvanic isolation. Automatically detects the operating voltage of the useful signal and optimally adjusts the protection level to this.