| Standards |
| Certification | UL |
| UL Standard | UL 497b |
| UL File Number | E156818 |
| Technical data |
| SPD class | M |
| Max. continuous operating voltage DC (UC) | 33 V |
| Nominal current at 45 °C (IL) | 0.75 A |
| D1 Total lightning impulse current (10/350 µs) (Iimp) | 10 kA |
| C2 Total nominal discharge current (8/20 µs) (In) | 20 kA |
| Series resistance per line | 1.8 Ohm |
| Cut-off frequency line-PG (fG) | 6.8 MHz |
| Approvals | CSA, UL 497B, ATEX, IECEx, CCC, CSA & USA Hazloc, SIL |
| Test values according to UL 497b |
| Type (SPD classification) | BXT ML4 BE 24 |
| Strike voltage Line to Ground 100 V/s min. | 35 V |
| Strike voltage Line to Ground 100 V/s max. | 42 V |
| Strike voltage Line to Line 100 V/s min. | 70 V |
| Strike voltage Line to Line 100 V/s max. | 83 V |
| Surge voltage Line to Ground 100 V/s min. | 35 V |
| Surge voltage Line to Ground 100 V/s max. | 45 V |
| Surge voltage Line to Line 100 V/s min. | 70 V |
| Surge voltage Line to Line 100 V/s max. | 90 V |
Space-saving combined surge arrester module with LifeCheck for protecting 4 individual wires with a common reference potential and asymmetrical interfaces. LifeCheck detects thermal or electrical overload conditions after which the surge arrester must be replaced. The indication is contactless using DEHNrecord LC / SCM / MCM.