| Technical data |
| SPD class | M |
| Max. continuous operating voltage DC (UC) | 33 V |
| Nominal current at 70 °C (IL) | 0.1 A |
| D1 Total lightning impulse current (10/350 µs) (Iimp) | 10 kA |
| C2 Total nominal discharge current (8/20 µs) (In) | 20 kA |
| Series resistance per line | typ. 10 Ohm |
| Cut-off frequency line-line (fG) | 4 MHz |
| Approvals | SIL |
Space-saving combination surge arrester module with LifeCheck for protecting 2 pairs of wires in 24 V DC systems. With integrated PTC resistors for overcurrent protection up to 40 A. LifeCheck detects thermal or electrical overload conditions after which the surge arrester must be replaced. The indication is contactless using DEHNrecord LC / SCM / MCM.