| General |
| Product type | combination arrester module |
| Degree of protection | for 1 pair cable |
| Interface | earth potential-free symmetrical interface |
| Shield grounding | Optional direct or indirect |
| Monitoring function | LifeCheck |
| Indication | contactless |
| Compatibility | DEHNrecord LC / SCM / MCM |
| Technical data |
| SPD class | M |
| Max. continuous operating voltage DC (UC) | 6.0 V |
| Nominal current at 45 °C (IL) | 1.0 A |
| D1 Total lightning impulse current (10/350 µs) (Iimp) | 9 kA |
| C2 Total nominal discharge current (8/20 µs) (In) | 20 kA |
| Series resistance per line | 1.0 Ohm |
| Cut-off frequency line-line (fG) | 1.0 MHz |
| Approvals | CSA, ATEX, IECEx, CSA & USA Hazloc, SIL |
The DEHN BXT ML2 BD S 5 is a space-saving surge protection module, specifically developed for the protection of a twisted pair cable at earth potential-free symmetrical interfaces. The module integrates the functions of a surge arrester and a monitoring system in a compact housing, making it particularly advantageous for use in installations with limited space. It protects data lines against overvoltages caused by lightning strikes or electrical disturbances, thereby ensuring the functionality and longevity of connected devices.
Applications
This module is intended for use in IT and telecommunications installations, particularly in systems communicating via earth potential-free symmetrical interfaces. Typical applications include protection installations in server rooms, network centers, telephone systems, or industrial control systems, where data transmission integrity is of high importance. The optional direct or indirect screen earthing allows flexible adaptation to different installation scenarios and protection concepts.
Functions and Equipment in Detail
A central feature of the module is the integrated LifeCheck function. This detects thermal or electrical overload conditions indicating damage to the surge arrester. After such an event, the arrester must be replaced to ensure continued protection. Monitoring is contactless, enabling continuous control without physical access. The display of status information is provided via DEHNrecord LC, SCM, or MCM, which serve as external monitoring units.
Technology Explained Simply
The surge arrester protects the connected twisted pair cable from transient overvoltages caused by external influences such as lightning discharges or inductive disturbances. The combination of direct and indirect screen earthing allows application-specific selection of the earthing method, enabling adaptation to existing systems. The LifeCheck function is based on an internal sensor that detects temperature and current changes and transmits these to the external monitoring unit. This ensures continuous status monitoring without additional installation effort.
Compatibility and Accessories
The module is designed for use with the monitoring units DEHNrecord LC, SCM, and MCM. These devices serve as interfaces for visual or digital display of the surge arster's status. Compatibility with these systems enables centralized monitoring of multiple arresters in a network, simplifying maintenance and fault diagnosis.
Mounting and Installation
Mounting is performed in standard installation rails, typically 35 mm DIN rails, installed in distribution boxes or enclosures. Installation requires no additional tools or components, except for the necessary connection elements for the cable. The optional screen earthing requires a decision during installation, depending on whether direct earthing of the screen or indirect earthing via a separate earthing path is desired.
Advantages in Operation
The use of the BXT ML2 BD S 5 provides a compact and efficient solution for overvoltage protection in data lines. The integrated LifeCheck function reduces maintenance costs, as the status of the surge arrester is continuously monitored and replacement is only required when actual damage has occurred. The contactless display via external devices enables centralized monitoring, increasing the availability and safety of the installation. The flexibility in screen earthing expands application possibilities in various installation scenarios.