| Standards |
| Certification | UL |
| UL Standard | UL 497b |
| UL File Number | E156818 |
| Technical data |
| SPD class | M |
| Max. continuous operating voltage DC (UC) | 45 V |
| Nominal current at 45 °C (IL) | 1.8 A |
| D1 Total lightning impulse current (10/350 µs) (Iimp) | 9 kA |
| C2 Total nominal discharge current (8/20 µs) (In) | 20 kA |
| Series resistance per line | 0.43 Ohm |
| Cut-off frequency line-PG (fG) | 3.8 MHz |
| Approvals | UL 497B, SIL |
| Test values according to UL 497b |
| Type (SPD classification) | BXT ML2 BE S 36 |
| Strike voltage Line to Ground 100 V/s min. | 50 V |
| Strike voltage Line to Ground 100 V/s max. | 56 V |
| Strike voltage Line to Line 100 V/s min. | 72 V |
| Strike voltage Line to Line 100 V/s max. | 112 V |
| Surge voltage Line to Ground 100 V/s min. | 50 V |
| Surge voltage Line to Ground 100 V/s max. | 56 V |
| Surge voltage Line to Line 100 V/s min. | 100 V |
| Surge voltage Line to Line 100 V/s max. | 112 V |
Space-saving combined surge arrester module with LifeCheck for protecting 2 individual wires with a common reference potential and asymmetrical interfaces, optionally direct or indirect shield earthing. LifeCheck detects thermal or electrical overload conditions after which the surge arrester must be replaced. The indication is made contactless using DEHNrecord LC / SCM / MCM.