| Technical data |
| SPD class | M |
| Max. continuous operating voltage DC (UC) | 33 V |
| Nominal current at 45 °C (IL) | 0.75 A |
| D1 Total lightning impulse current (10/350 µs) (Iimp) | 9 kA |
| C2 Total nominal discharge current (8/20 µs) (In) | 20 kA |
| Series resistance per line | 1.8 Ohm |
| Cut-off frequency line-PG (fG) | 6.8 MHz |
| Approvals | CSA, ATEX, IECEx, CCC, CSA & USA Hazloc, SIL |
Space-saving combined surge arrester module with LifeCheck for protecting 2 individual wires with a common reference potential and asymmetrical interfaces, optionally direct or indirect shield earthing. LifeCheck detects thermal or electrical overload conditions after which the surge arrester must be replaced. The indication is made contactless using DEHNrecord LC / SCM / MCM.