Further information for DEHN 909657 SET 3 DSH ZP B2 LSG TT + 1X DSHU 3P 50
Extended technical data: DSH ZP B2 LSG TT 255
Protection level [L-PE] (UP)
≤ 1,6 kV
Technical data: DSH ZP B2 LSG TT 255
SPD according to EN 61643-11 / IEC 61643-11
Type 1 + Type 2 + Type 3 / Class I + Class II + Class III
Energy-coordinated protective effect to end device (≤ 10 m)
Type 1 + Type 2 + Type 3
Nominal voltage AC (UN)
230 / 400 V (50 / 60 Hz)
Maximum continuous voltage AC (UC)
255 V (50 / 60 Hz)
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal)
30 kA
Lightning impulse current (10/350 µs) [L-N] (Iimp)
7,5 kA
Specific energy [L-N] (W/R)
14.06 kJ/Ohm
Lightning impulse current (10/350 µs) [N-PE] (Iimp)
30 kA
Specific energy [N-PE] (W/R)
225 kJ/Ohm
Rated discharge current (8/20 µs) [L-N]/[N-PE] (In)
20 / 80 kA
Protection level [L-N] (UP)
≤ 1,5 kV
Protection level [N-PE] (UP)
≤ 1,5 kV
No-load voltage of hybrid generator (UOC)
20 kV
Max. mains-side overcurrent protection
160 A gG
TOV voltage [L-N] (UT) – characteristic
440 V / 120 min. – withstand
TOV voltage [N-PE] (UT) – characteristic
1200 V / 200 ms – withstand
Operating temperature range (TU)
-40 °C ... +80 °C
Function / fault indicator
green / red
Number of ports
1
Connection cross-section (PEN, 9 )
16-25 mm2 fine-stranded / 16-35 mm2 stranded
Mounting on
40-mm busbar system
Housing material
Thermoplastic, colour red, UL 94 V-0
Mounting position
Indoor
Degree of protection
IP 30 (with cover)
Mounting dimensions
3 TE, DIN 43880
Approvals
VDE
Supply voltage (for RfZ/APZ according to VDE-AR-N 4100) (UN)
230 V
Compatible circuit breakers (manufacturer, type)
ABB S201P-B6, Hager MB199
Rated current of circuit breaker (In)
6 A
Release characteristic
B
Technical data: DSHU 3P ..
Function
single-pole switching
Insulation test voltage at 50/60 Hz - 1 min
2 kV
Power supply system
Any
Switch position indicator
Red ON / Green OFF
Tightening moment
2,5 ... 3 Nm
Operating part design
toggle handle
Recommended screwdriver
Phillips No. 2 Pozidriv, slot 1 x 5.5
Tripping characteristic (selective)
E
Rated operating voltage (AC)
230 / 400 V
Rated insulation voltage according to IEC / EN 60664-1 (Ui)
690 V
Rated impulse withstand voltage (Uimp)
6 kV
Rated impulse voltage withstand at 2000 m (Uimp)
8 kV
Input voltage type
AC
Rated current (In)
50 A
Rated switching capacity (230 / 400 V AC)
25 kA
Rated frequency (f)
50 / 60 Hz
Power loss under rated conditions per pole
6.9 W
Over voltage category
IV
Ambient temperature (in operation)
-25 ... +55 °C
Ambient temperature (storage)
-40 ... +70 °C
Pollution degree
3
Dimensions
4.5 TE, DIN 43880
Standards
DIN VDE 0641-21
Disconnect function
Set aus Kombi-Ableiter Typ 1 + Typ 2 + Typ 3 nach EN 61643-11 für TT- und TN-S-Systeme (3+1-Schaltung) und selektivem Haupt-Leitungsschutzschalter DSHU. Nachträgliche Integration eines einpoligen B6 Leitungsschutzschalters möglich zur Realisierung einer Spannungsversorgung des intelligenten Messystems. Zwei Buchsen für die 230 V Spannungsversorgung (N und L) jeweils für RfZ / APZ gem. VDE-AR-N 4100 sind im Gerät integriert, zum Einsatz auf dem 40 mm Sammelschienensystem im Hauptstromversorgungssystem nach DIN VDE 0100-443 bei Gebäuden ohne äußeres Blitzschutzsystem (auch mit Freileitungseinspeisung), direkte Einspeisung der Außenleiter am selektiven Hauptleitungsschutzschalter, sperr und plombierbar mit einem Bemessungsschaltvermögen von 25 kA nach DIN VDE 0100-537 bzw. DIN EN 60947 nach Charakteristik E.