| General |
| SPD class | O |
| Nominal voltage (UN) | 24 V |
| Max. continuous operating voltage DC (UC) | 28 V |
| Max. continuous operating a.c. voltage (UC) | 19.5 V |
| Nominal current (IN) | 0.4 A |
| D1 Total lightning impulse current (10/350 µs) in combination with DRL 10 B... (Iimp) | 5 kA |
| D1 Lightning impulse current (10/350 µs) per line in combination with DRL 10 B... (Iimp) | 2.5 kA |
| C2 Total nominal discharge current (8/20 µs) in combination with DRL 10 B... (In) | 10 kA |
| C2 Nominal discharge current (8/20 µs) per line in combination with DRL 10 B... (In) | 5 kA |
| C1 Nominal discharge current (8/20 µs) per line without DRL 10 B... (In) | 0.5 kA |
| Voltage protection level line-PG for Iimp D1 in combination with DRL 10 B... (UP) | ≤ 500 V |
| Voltage protection level line-line at 1 kV/µs C3 (UP) | ≤ 36 V |
| Series impedance per line | 2.2 ohms |
| Cut-off frequency line-line (fG) | 5.4 MHz |
| Capacitance line-line (C) | ≤ 1.1 nF |
| Operating temperature range (TU) | -40 °C ... +80 °C |
| Degree of protection | IP 20 (when plugged in) |
| Pluggable into | LSA disconnection block 2/10 or DRL 10 B ... plug-in SPD block |
| Enclosure material | polyamide PA 6.6 |
| Colour | yellow |
| Test standards | IEC 61643-21 / EN 61643-21 |
Protective plug 1 DA energetically coordinated with DRL plug-in magazine as single-stage terminal device protection. Low protection level wire-wire for earth-potential-free interfaces. Installation with EF 10 DRL. Installation only recommended in conjunction with the DRL plug-in magazine.