| General |
| SPD according to EN 61643-11 / IEC 61643-11 | type 2 + type 3 / class II + class III |
| Tested to | EN 61439-1 / ... IEC 61439-1, EN 61439-2 / ... IEC 61439-2 |
| Nominal voltage (a.c.) (UN) | 230 V (50 / 60 Hz) |
| Nominal alternating current (IL) | 16 A |
| Max. power | 11 kW |
| Voltage protection level [L-N] (UP) | ≤ 1.5 kV |
| Voltage protection level [N-PE] (UP) | ≤ 1.5 kV |
| Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 335 V / 5 sec. – withstand, 440 V / 120 min. – safe failure |
| Temporary overvoltage (TOV) [N-PE] (UT) - Characteristic | 1200 V / 200 ms. – withstand |
| Operating state / fault indication | green / red |
| Type of remote signalling contact | changeover contact |
| Switching capacity (a.c.) | 250 V / 0.5 A |
| Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
| Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
| Place of installation | Installation in protected outdoor areas |
| Degree of protection | IP 65 |
| Type | with pressure compensating element |
| Cover | Transparent cover with product label |
| Enclosure colour | grey |
| Input | Ölflex 5x 4 mm², length 1.5 m |
| Output | System-side connection with M25 screw connection |
| Enclosure dimensions (W x H x D) | 110 x 110 x 66 mm |
Housing connection box DCU EMOB 2 16, Type 2 + Type 3, with protection class IP 65, according to DIN EN IEC 61643-11 and 61439-2, for universal installation in front of the wallbox.