| SPD according to EN 61643-11 / IEC 61643-11 | type 3 / class III |
| Max. continuous operating voltage (AC) (UC) | 280 V (50 / 60 Hz) |
| Nominal discharge current (8/20 µs) (In) | 3 kA |
| Total discharge current (8/20 µs) [L+N-PE] (Itotal) | 5 kA |
| Voltage protection level [L-N] / [L/N-PE] (UP) | ≤ 1250 / ≤ 1500 V |
| Max. mains-side overcurrent protection | B 16 A |
| Fault indication | remote signalling contact (break contact) |
Two-pole surge arrester VC 280 2, type 3 according to EN 61643-11, with monitoring device and disconnection device. Increased safety through confusion-proof Y-protective circuit. For protecting electronic devices against overvoltages. For installation in housings or directly in the device to be protected. For use in the lightning protection zone concept at interfaces 1 - 2 and higher.