| General |
| SPD according to EN 61643-11 / IEC 61643-11 | Type 2 / class II |
| Energy coordination with terminal equipment (≤ 10 m) | Type 2 + type 3 |
| Nominal voltage (a.c.) (UN) | 230 V (50 / 60 Hz) |
| Max. continuous operating voltage (AC) (UC) | 280 V (50 / 60 Hz) |
| Nominal discharge current (8/20 µs) (In) | 15 kA |
| Max. discharge current (8/20 µs) (Imax) | 30 kA |
| Voltage protection level (UP) | ≤ 1.5 kV |
| Voltage protection level at 5 kA (UP) | ≤ 1.2 kV |
| Response time (tA) | ≤ 25 ns |
| Max. mains-side overcurrent protection | not required |
| Rated breaking capacity of the internal backup protection | 25 kA |
| Short-circuit withstand capability (ISCCR) | 25 kArms |
| Temporary overvoltage (UT) – characteristic | 335 V / 5 sec. – withstand, 440 V / 120 min. – safe failure |
| Indication of disconnector | red indicator |
| Indicator for remote signalling | tripping distance of 7 mm |
| Number of ports | 1 |
| Operating temperature range (TU) | -40 °C ... +80 °C |
| For mounting on | NH fuse holder, size 00 |
| Enclosure material | Thermoplastic, red, UL 94 V-0 |
| Place of installation | Indoor |
| Degree of protection | IPX4W |
1-pole surge arrester for use
in NH fuse holders size 00
with signal for remote signaling
Arrester
Type 2 according to EN 61643-11
Heavy-duty varistor technology
Fault indication by tripping indicator,
for remote signaling using NH-fuse
divide with micro switch possible
(tripping signal pin max 7 mm.)
Maximum continuous voltage: 280V AC
Protection level
at 5 kA (8 / 20): <1 kV
at 15 kA (8/20): <1.25 kV
nominal discharge current: 15 kA (8/20)
Max. Discharge current: 30 kA (8/20)
Energy coordination in accordance with DIN EN 62305-4 (VDE 0185-
305-4) with
type 1 and
type 3 arresters of the Red / Line family
Mounting on NH fuse bases size 00; Type: V NH00 280 FM