| General |
| SPD according to EN 61643-11 / IEC 61643-11 | type 2 / class II |
| Energy coordination with terminal equipment (≤ 10 m) | type 2 + type 3 |
| Nominal voltage (a.c.) (UN) | 230 V (50 / 60 Hz) |
| Max. continuous operating voltage (AC) (UC) | 280 V (50 / 60 Hz) |
| Nominal discharge current (8/20 µs) (In) | 15 kA |
| Max. discharge current (8/20 µs) (Imax) | 30 kA |
| Voltage protection level (UP) | ≤ 1.5 kV |
| Voltage protection level at 5 kA (UP) | ≤ 1.2 kV |
| Response time (tA) | ≤ 25 ns |
| Max. mains-side overcurrent protection | not required |
| Rated breaking capacity of the internal backup protection | 25 kA |
| Short-circuit withstand capability (ISCCR) | 25 kArms |
| Temporary overvoltage (UT) – characteristic | 335 V / 5 sec. – withstand, 440 V / 120 min. – safe failure |
| Indication of disconnector | red indicator |
| Number of ports | 1 |
| Operating temperature range (TU) | -40 °C ... +80 °C |
| For mounting on | NH00 fuse holders |
| Enclosure material | thermoplastic, red, UL 94 V-0 |
| Place of installation | indoor installation |
| Degree of protection | IPX4W |
Single-pole surge arrester V NH, type 2 according to EN 61643-11 in NH design with integrated arrester backup fuse. For protecting low-voltage consumer systems against overvoltages. For use in the lightning protection zone concept at the interfaces 0B - 1 and higher.