| General |
| Degree of protection | Type 1 + Type 2 |
| Norm | EN 61643-31 |
| Application | Photovoltaic generator circuits |
| Nominal voltage | 1500 V DC |
| Switching device | 3-stage DC switching device |
| Function | combined disconnect and short-circuit device |
| Application standard | IEC 60364-7-712:2002-05 |
| Technical data |
| SPD according to EN 61643-31 / IEC 61643-31 | Typ 1 + Typ 2 / Class I + Class II |
| Max. PV voltage [DC+ - DC-] (UCPV) | ≤ 1500 V |
| Short-circuit withstand capability (ISCPV) | 10 kA |
| Total discharge current (10/350 µs) [DC+/DC- - PE] (Itotal) | 12,5 kA |
| Lightning impulse current (10/350 µs) [DC+ - PE/DC- - PE] (Iimp) | 6,25 kA |
| Voltage protection level [(DC+/DC-) - PE] (UP) | < 4,5 kV |
| Approvals | KEMA, UL |
The DEHNcombo YPV 1500 is a multipole combination surge arrester for photovoltaic generator circuits, developed to protect photovoltaic inverters against overvoltages. The arrester combines the protective functions of Type 1 and Type 2 according to EN 61643-31 and is specifically designed for use in photovoltaic systems with a nominal voltage of 1500 V DC. It protects against transient overvoltages caused by direct lightning strikes or inductive voltage surges, ensuring the safety of the installation during operation. Compliance with the standard IEC 60364-7-712:2002-05 for the installation of photovoltaic supply systems is guaranteed by the arrester.
Applications
The DEHNcombo YPV 1500 is designed for use in photovoltaic installations, particularly in those with high DC voltages up to 1500 V. It is typically installed in the generator circuit to protect inverters and other sensitive electronic components from overvoltages. The application is in industrial and commercial photovoltaic systems where high reliability and protective function are required. The standard IEC 60364-7-712:2002-05 defines the requirements for the installation of such systems, with the arrester being part of the overvoltage protection measures.
Functions and Equipment in Detail
The arrester features a 3-stage DC switching device that enables combined disconnection and short-circuit protection functions. This function ensures that in the event of a fault, the affected circuit is safely disconnected to prevent hazards from short circuits or further overvoltages. The combination of Type 1 and Type 2 protection provides comprehensive protection, with Type 1 responsible for direct lightning strikes and Type 2 for indirect overvoltages. The switching device is designed to react quickly to overvoltages and activate the protection circuit.
Technology Explained Simply
The technology of the DEHNcombo YPV 1500 is based on the combination of overvoltage protection and switching functions. The 3-stage DC switching device enables selective disconnection of the affected circuit without having to shut down the entire photovoltaic generator. The protective functions comply with the requirements of the standard EN 61643-31, which was specifically developed for overvoltage protection devices in photovoltaic systems. The DC switching device is designed for operation in high-voltage installations and ensures safe disconnection in the event of a fault.
Compatibility and Accessories
The arrester is designed for photovoltaic systems with a nominal voltage of 1500 V DC and can be used in systems requiring this voltage level. Compatibility with other components of the photovoltaic installation, such as inverters or fuses, is covered by the standard IEC 60364-7-712:2002-05.
Mounting and Installation
Installation is carried out in accordance with the requirements of the standard IEC 60364-7-712:2002-05. The arrester is intended for installation in photovoltaic generator circuits and must be installed at an appropriate location in the circuit to ensure optimal protective function. Installation requires compliance with electrical safety regulations and correct connection of the conductors. The 3-stage DC switching device must be connected according to technical requirements to ensure proper function.
Advantages in Operation
The DEHNcombo YPV 1500 provides comprehensive protection for photovoltaic inverters and other sensitive components. The combination of Type 1 and Type 2 protection ensures high reliability, even in the event of direct lightning strikes. The 3-stage DC switching device enables selective disconnection, limiting the disturbance to the affected area. Compliance with the standard IEC 60364-7-712:2002-05 ensures conformity with current safety standards for photovoltaic systems. The arrester is thus an integral part of the safety architecture in modern photovoltaic installations.