| Technical data |
| SPD according to EN 61643-31 / IEC 61643-31 | Typ 1 + Typ 2 / Class I + Class II |
| Max. PV voltage [DC+ - DC-] (UCPV) | ≤ 1200 V |
| Short-circuit withstand capability (ISCPV) | 10 kA |
| Total discharge current (10/350 µs) [DC+/DC- - PE] (Itotal) | 12,5 kA |
| Lightning impulse current (10/350 µs) [DC+ - PE/DC- - PE] (Iimp) | 6,25 kA |
| Voltage protection level [(DC+/DC-) - PE] (UP) | < 3,8 kV |
| Approvals | KEMA, UL |
Combined arrester DEHNcombo YPV 1200
Multi-pole combination arrester type 1 + type 2
for photovoltaic generator circuits up to 1200 V DC
with 3-stage DC switching device, width 4TE
Type 1 + type 2 arrester according to EN 50539-11
Can be used in accordance with IEC 60364-7 -712
Combined disconnection and short-circuiting
device Defect display
Maximum PV voltage: < 1200 V dc
Total leakage surge current: 12.5 kA
Protection level: < 3.8 kV
Short-circuit strength Iscpv: 10 kA