| General |
| Diameter Ø conductor | 8 mm |
| Cross section | 50 mm² |
| Material | Al |
| Properties | soft |
| Standard | EN 62561-2 |
| Diameter Ø outside | 11 mm |
| Sheath material | plastic |
| Sheath thickness | 1.5 mm |
| Specific conductance | ≥ 27.77 m / Ohm mm² |
| Specific resistance | ≤ 0.036 Ohm mm² / m |
| Short-circuit current (AC 50 Hz / DC) (1 s; ≤ 300 °C) | 6.4 kA |
| Length tolerance | +/- 5% |
The DEHN round wire type RD 8 AL WE KM R100M is an aluminium branch wire for lightning protection and earthing systems, compliant with standard DIN EN 62561-2 (VDE 0185-561-2). It serves as a conductor in external lightning protection systems and is particularly used for installation behind facades or in areas with increased mechanical stress. The wire features a plastic sheath that provides additional protection against mechanical damage and corrosion. The sheath is halogen-free, frost-resistant, and UV-stabilised, making it suitable for outdoor use. Installation in the ground is not intended, as the plastic sheath is not designed for direct soil contact.
Applications
The round wire is intended for use in lightning protection systems, particularly as a conductor for lightning currents from the capture or down-conductor system to the earthing system. It is suitable for installation in buildings where mechanical stress or environmental influences such as UV radiation and frost occur. Installation typically takes place behind facades, in channels, or in other protected areas, but not in the ground. The standard DIN EN 62561-2 ensures that the wire meets the required electrical and mechanical specifications for use in lightning protection systems.
Functions and Equipment in Detail
The wire consists of soft aluminium (Al) with a conductor diameter of 8 mm and a cross-section of 50 mm². The soft material property allows for easy bending and installation, which is advantageous when installing in complex geometries. The plastic sheath has an outer diameter of 11 mm and a sheath thickness of 1.5 mm. It protects the conductor from external influences and extends the wire’s service life. The sheath colour corresponds to RAL light grey 7035, facilitating visual identification and integration into building elements.
Technology Explained Simply
The specific conductivity is at least 27.77 m / Ohm mm², corresponding to the specific electrical conductivity typical for aluminium of this quality. The specific resistance is at most 0.036 Ohm mm² / m, quantifying the material’s electrical conductivity. These values ensure efficient current conduction under high currents, such as those occurring during lightning strikes. The short-circuit current is 6.4 kA for a duration of 1 second and a maximum temperature of 300 °C, describing the wire’s thermal and mechanical load capacity under extreme conditions. The length tolerance is ±5 %, which must be considered during processing.
Compatibility and Accessories
The wire is designed for use with other components of lightning protection systems, such as cross or T-connectors, pipe clamps, and equipotential bonding bars. Connections are typically made using mechanical or screwed connections, which must also comply with lightning protection standards. Using accessories not from the same standard series may impair the system’s functionality. The wire is supplied in ring lengths of 100 m, with a net weight of approximately 200 g/m.
Installation and Mounting
Installation is typically carried out by specialists in lightning protection technology. The wire is laid along the designated route, taking into account bending radii and mechanical stress. Connection points must be secure and durable to ensure continuous electrical conductivity. Installation in the ground is not intended, as the plastic sheath is not designed for this application. Installation generally takes place in protected areas, such as behind facades or in channels, to protect the sheath from direct contact with moisture, soil, or mechanical impacts.
Advantages in Operation
The DEHN round wire offers high electrical conductivity and mechanical flexibility, simplifying installation and enhancing the reliability of the lightning protection system. The plastic sheath protects the conductor from corrosion and mechanical damage, extending the wire’s service life. Compliance with DIN EN 62561-2 ensures that the wire meets the required specifications for use in lightning protection systems. Installation in protected areas enables long-term functionality without additional protective measures.