| General |
| Material of air-termination tip | StSt |
| Length of air-termination rod | 1000 mm |
| Material of supporting tube | GRP / Al |
| Length of supporting tube | 1600 mm |
| Transport length | 1600 mm |
| Diameter Ø outside | 40 mm |
| Diameter Ø conductor | 21 mm |
| Colour of conductor | Grey ● |
| Material of conductor | Cu |
| RAL colour | similar to 7004 |
| Cross-section of core (solid) | 16 mm² |
| Lightning current carrying capability (class / Iimp) | H1 / 150 kA |
| Equivalent separation distance s (air) | ≤ 60 cm |
| Material of insulation | PE |
| Sheath material | PE |
| Characteristics of sheath | UV-stabilised and weather resistant |
| Connection diameter | 10 mm |
| Material of connection elements | StSt |
| Supporting tube | 40 x 4 mm |
| Minimum order length | 6 m |
| Pull-out force with a length of 500 mm | 200 N (supporting tube insulator as per 62561-8) |
| Bending force with a length of 500 mm | 200 N (supporting tube insulator as per 62561-8) |
| Standard | DIN EN IEC 62561-8 (VDE 0185-561-8) |
HVI light plus Leitung (Hochspannungsfeste isolierte Ableitung) im Stützrohr, zum Einhalten des Trennungsabstandes zu elektrisch leitenden Teilen nach DIN EN 62305-3 (VDE 0185-305-3), um gefährliche Überschläge zwischen Teilen des Äußeren Blitzschutzes und inneren, leitfähigen Teilen (Elektroanlage, Rohrleitungen, usw.) zu verhindern. Um Gleitentladungen zu vermeiden, ist die HVI light plus Leitung mit einem äußeren Spezialmantel ausgestattet, der es ermöglicht, hohe Blitz-Impulsspannungen gegen ein Bezugspotential ab zusteuern. Ausführung HVI light plus Leitung (grau), mit innenliegendem Endverschluss und PA-Federelement im Stützrohr (Länge 1600 mm) mit Fangspitze (D10 mm Länge 1000 mm) und einem Erdanschlusselement. Äquivalenter Trennungsabstand s = 60 cm (in Luft), s = 120 cm (fester Baustoff).