| General |
| Material of air-termination tip | Al |
| Length of air-termination rod | 2500 mm |
| Material of supporting tube | GRP / Al |
| Length of supporting tube | 4700 mm |
| Transport length | 4700 mm |
| Diameter Ø outside | 50 mm |
| Diameter Ø conductor | 20 mm |
| Colour of conductor | black ● |
| Material of conductor | Cu |
| RAL colour | similar to 9011 |
| Cross section of core (stranded) | 19 mm² |
| Lightning current carrying capability (class / Iimp) | H1 / 150 kA |
| Equivalent separation distance s (air) | ≤ 75 cm |
| Material of insulation | PE |
| Sheath material | PE |
| Characteristics of sheath | UV-stabilised and weather resistant |
| Connection diameter | 10 mm |
| Material of connection elements | StSt |
| Supporting tube | 50 x 4 mm |
| Radius of tripod | 1330 mm |
| Space required for tripod | 2300 x 1995 mm |
| Length of threaded rods | M16 x 650 mm |
| Minimum order length | 6 m |
| Pull-out force with a length of 500 mm | 200 N (supporting tube insulator as per 62561-8) |
| Bending force with a length of 500 mm | 200 N (supporting tube insulator as per 62561-8) |
| Standard | DIN EN IEC 62561-8 (VDE 0185-561-8) |
HVI Leitung (Hochspannungsfeste isolierte Ableitung) im Stützrohr, zum Einhalten des Trennungsabstandes zu elektrisch leitenden Teilen nach DIN EN 62305-3 (VDE 0185-305-3), um gefährliche Überschläge zwischen Teilen des Äußeren Blitzschutzes und inneren, leitfähigen Teilen (Elektroanlage, Rohrleitungen, usw.) zu verhindern. Um Gleitentladungen zu vermeiden, ist die HVI Leitung mit einem äußeren Spezialmantel ausgestattet, der es ermöglicht, hohe Blitz-Impulsspannungen gegen ein Bezugspotential ab zusteuern. Ausführung HVI Leitung (schwarz), mit innenliegendem Endverschluss und PA-Federelement im Stützrohr (Länge 4700 mm) mit Fangstange (D22 /16 / 10 mm Länge 2500 mm), Erdanschlusselement und Dreibeinstativ. Äquivalenter Trennungsabstand s = 75 cm (in Luft), s = 150 cm (fester Baustoff).