| General |
| Material of air-termination rod | Al |
| Length of air-termination rod | 2500 mm |
| Material of supporting tube | GRP / Al |
| Length of supporting tube | 3200 mm |
| Transport length | 3200 mm |
| Diameter Ø outside | 50 mm |
| Diameter Ø conductor | 20 mm |
| Colour of conductor | black ● |
| Material of conductor | Cu |
| RAL colour | similar to 9011 |
| Cross section of core (stranded) | 19 mm² |
| Lightning current carrying capability (class / Iimp) | H1 / 150 kA |
| Equivalent separation distance s (air) | ≤ 75 cm |
| Material of insulation | PE |
| Sheath material | PE |
| Characteristics of sheath | UV-stabilised and weather resistant |
| Connection diameter | 10 mm |
| Material of connection elements | StSt |
| Supporting tube | 50 x 4 mm |
| Radius of tripod | 680 mm |
| Space required for tripod | 1175 x 1020 mm |
| Length of threaded rods | M16 x 520 mm |
| Minimum order length | 6 m |
| Pull-out force with a length of 500 mm | 200 N (supporting tube insulator as per 62561-8) |
| Bending force with a length of 500 mm | 200 N (supporting tube insulator as per 62561-8) |
| Standard | DIN EN IEC 62561-8 (VDE 0185-561-8) |
HVI cable (high-voltage-resistant insulated conductor) in a support tube, to maintain the separation distance from electrically conductive parts in accordance with DIN EN 62305-3 (VDE 0185-305-3), in order to prevent dangerous flashovers between parts of the external lightning protection and internal, conductive parts (electrical system, pipes, etc.). To prevent creeping discharges, the HVI cable is equipped with a special external sheath that enables high lightning impulse voltages to be diverted to a reference potential. HVI cable design (black), with internal end closure and PA spring element in the support tube (length 3200 mm) with air-termination rod (D22 /16 / 10 mm length 2500 mm), earth connection element and tripod. Equivalent separation distance s = 75 cm (in air), s = 150 cm (solid building material).