| General |
| Material of air-termination rod | Al |
| Length of air-termination rod | 2500 mm |
| Material of supporting tube | GRP / Al |
| Length of supporting tube | 3200 mm |
| Transport length | 3200 mm |
| Diameter Ø outside | 50 mm |
| Diameter Ø conductor | 23 mm |
| Colour of conductor | grey ● |
| Material of conductor | Cu |
| RAL colour | similar to 7035 |
| Cross section of core (stranded) | 19 mm² |
| Lightning current carrying capability (class / Iimp) | H1 / 150 kA |
| Equivalent separation distance s (air) | ≤ 75 cm |
| Material of insulation | PE |
| Sheath material | PE |
| Characteristics of sheath | UV stabilised and weather resistant |
| Connection diameter | 10 mm |
| Material of connection elements | StSt |
| Supporting tube | 50 x 4 mm |
| Minimum order length | 6 m |
| Max. free length with air-termination rod (wall mounting) | 5000 mm |
| Max. gust wind speed | (max. free length 5000 mm, 1x HVI grey inside) 189, (max. free length 5000 mm, 1x HVI grey outside) 173, (max. free length 5000 mm, 4x HVI grey outside) 151 km/h |
| Pull-out force with a length of 500 mm | 200 N (supporting tube insulator as per 62561-8) |
| Bending force with a length of 500 mm | 200 N (supporting tube insulator as per 62561-8) |
| Standard | DIN EN IEC 62561-8 (VDE 0185-561-8) |