The DEHN potential equalisation bar for industrial applications, type PAS I 8AP M10 CU, is an earthing component made of copper (Cu) for use in industrial electrical installations. It serves for protective and functional potential equalisation in accordance with DIN VDE 0100 Part 410/540, as well as for lightning protection potential equalisation according to DIN EN 62305-3 (VDE 0185-305-3). The bar features eight connection points and is suitable for use in Ex zones, with screws secured against self-loosening. The construction includes insulators made of duroplastic material (UP), which are red-coloured, UV-stabilised, and halogen-free. The screws have an M10 thread with a length of 25 mm and are made of NIRO material, supplemented by spring washers for a secure connection.
Applications
The bar is designed for use in industrial plants where reliable potential equalisation is required to avoid electrical hazards. It is used within lightning protection systems and protective measures against electrical disturbances. The UV resistance of the insulators also makes it suitable for outdoor applications. The approval for Ex zones (Zone 2/22) extends its use to explosive environments, with mechanical security of the screw connections guaranteed.
Functions and Equipment in Detail
The bar provides eight connection points, each equipped with an M10 screw, a spring washer, and a nut. The spring washers ensure a durable, corrosion-resistant connection that remains stable even under mechanical stress. The UP material insulators are marked red and prevent unwanted electrical connections between the terminals. The UV stabilisation protects the insulators from ageing due to sunlight exposure, increasing the service life of the bar.
Technology Explained Simply
The bar has a cross-section of 200 mm² and is designed for a short-circuit current of 39 kA (AC 50 Hz / DC) over a duration of 1 second and a maximum temperature of 300 °C. These values ensure sufficient thermal and mechanical load capacity in case of sudden current surges, such as those occurring during short circuits or lightning strikes. The dimensions are 365 mm in length, 40 mm in width, and 5 mm in thickness, enabling compact mounting in enclosures or on mounting plates. The use of copper as the material ensures high electrical conductivity and corrosion resistance.
Compatibility and Accessories
The bar is designed for use in systems complying with the standards DIN EN 62561-1, DIN VDE 0100 Part 410/540, and DIN EN 62305-3 (VDE 0185-305-3). It can be combined with other DEHN earthing components to build complex earthing systems. The use of NIRO screws and spring washers enables secure mounting that remains stable even in humid or corrosive environments. The UP material insulators are halogen-free, increasing safety in case of fire.
Mounting and Installation
Mounting is done via screw connections at the designated connection points. The spring washers ensure a secure connection that does not loosen even under vibrations or temperature fluctuations. The M10 screws allow for simple and standardised installation. The bar can be mounted in enclosures, on mounting plates, or in other industrial installations. The UV resistance of the insulators also permits outdoor use.
Operational Advantages
The bar offers high thermal and mechanical load capacity, making it suitable for critical applications. The UV stabilisation of the insulators extends service life, especially in outdoor installations. The approval for Ex zones expands the range of applications in hazardous environments. The use of copper and NIRO materials ensures high corrosion resistance and electrical conductivity. The eight connection points allow flexible integration into existing earthing systems.
The bar complies with the standards DIN EN 62561-1, DIN VDE 0100 Part 410/540, and DIN EN 62305-3 (VDE 0185-305-3), ensuring its suitability for professional installations. The UV resistance of the insulators and the protection against self-loosening of the screws increase reliability in operation. The dimensions and cross-section are designed for industrial requirements, with the thermal load capacity of 39 kA ensuring safe operation during short-circuit events.