| General |
| Manufacturer | DEHN |
| Material | StSt |
| Degree of protection | NIRO |
| Pipe diameter | 26,9 mm |
| Connection diameter | 11 mm |
| Screw size | M10 |
| Round conductor diameter | 7-10 mm |
| Clamping range for pipe Ø | 27 mm |
| Compliance with standards | DIN EN 62561-1, DIN VDE 0100-410/540, DIN EN 62305-3 (VDE 0185-305-3) |
| Dimension (l1 x r1) | 115.5 x 13.5 mm |
| Standard | EN 62561-1 |
The DEHN earthing pipe clamp type ERS 27 AB11 V2A is a component for lightning and electrical protection, specifically designed for integrating pipes into the protective and functional equipotential bonding. The product is manufactured from NIRO material (V2A steel) and serves to securely connect metallic pipe lines to the earthing system. It is intended for use in electrical installations in accordance with DIN VDE 0100-410/540 and in lightning protection systems according to DIN EN 62305-3 (VDE 0185-305-3). The clamp allows connection of round conductors with a diameter of 7 to 10 mm, for example via KS connectors, and provides a connection for flat conductors via screws and nuts M10.
Applications
The earthing pipe clamp is used in electrical installations where metallic pipe lines (e.g. water, gas, or heating pipes) must be integrated into the earthing system to avoid potential differences. This is particularly required in the field of lightning protection and protective equipotential bonding to ensure the safety of persons and installations. The clamp is intended for use in buildings and technical installations where a reliable earthing connection is necessary.
Functions and equipment in detail
The clamp is equipped with M10 screws, enabling a secure connection to the pipe. The connection for flat conductors is also made via screws and nuts M10, ensuring a safe and durable connection to the earthing system. The construction from NIRO material (V2A steel) offers high corrosion resistance and is therefore suitable for use in damp or aggressive environments. The clamp is designed for pipes with a diameter of 26.9 mm, with a conductor connection diameter of 11 mm.
Technology explained simply
The earthing pipe clamp serves as an interface between metallic pipe lines and the earthing system. By connecting, it ensures that all metallic parts of a building are at the same potential, preventing dangerous voltages from occurring during a lightning strike or electrical faults in the power supply system. The use of V2A steel ensures a long service life, even in damp or corrosive environments. The screw connections with M10 thread enable a mechanically stable and electrically conductive connection.
Compatibility and accessories
The clamp is suitable for round conductors with a diameter of 7 to 10 mm, for example in combination with KS connector systems. The connection for flat conductors is made via screws and nuts M10, enabling connection to standard earthing conductors. The clamp is compliant with lightning protection systems according to DIN EN 62305-3 and protective and functional equipotential bonding according to DIN VDE 0100-410/540.
Installation and mounting
Mounting is carried out by securing the clamp to the pipe using the integrated M10 screws. The connection to the earthing system is established via the flat conductor connection point using screws and nuts M10. The clamp is designed to ensure a mechanically secure and electrically conductive connection. Installation requires no special tools other than a screwdriver or an appropriate wrench for M10 screws.
Advantages in operation
The use of the DEHN earthing pipe clamp ensures a reliable and durable connection between metallic pipe lines and the earthing system. The construction from V2A steel guarantees high corrosion resistance, extending the service life of the component. The screw connections with M10 thread allow for easy and secure installation. The clamp is suitable for use in installations according to DIN EN 62305-3 and DIN VDE 0100-410/540, ensuring compliance with applicable standards.