| General |
| Norm | DIN EN 62561-1 |
| Type of connection | T-, cross- and parallel connections |
| Compatibility with round conductor | 6-20 mm |
| Flat cable compatibility | 30x3-4 mm |
| Application range | Concrete foundation, reinforced concrete mesh, reinforcement steels |
| Material | St/bare |
| Clamping range Rd / Rd | (+/II) 6-20 / 8-10 mm |
| Clamping range Rd / Fl | (+/II) 6-20 / 30 x 3-4 mm |
| Clamping range Fl / Fl | (+/II) 30 x 3-4 / 30 x 3-4 mm |
| Type | Without clamping ring |
| Short-circuit current (AC 50 Hz / DC) (1 s; ≤ 300 °C) | 8.4 kA |
| Standard | EN 62561-1 |
The DEHN compression clamp type VK DB 6.20 8.10 FL30 BSB STBL is a component for earthing systems, specifically designed for secure and durable connection of round and flat conductors with reinforcement steel in concrete foundations or reinforcement mesh. The product is manufactured in accordance with the standard DIN EN 62561-1, which defines requirements for the construction and testing of connection elements for lightning protection and earthing systems. The clamp is suitable for various connection types, including T-, cross- and parallel connections, thus enabling flexible adaptation to different construction site conditions and structures.
Applications
The compression clamp is used in the field of lightning protection and earthing technology, particularly in concrete structures, where metallic conductors must be connected to reinforcement steel. It serves to create an electrically conductive, mechanically stable, and corrosion-resistant transition between different conductor cross-sections. Typical applications include connecting round and flat conductors with reinforcement mesh or reinforcement steel in foundations, walls, or ceilings, to ensure an effective earthing system.
Functions and Equipment in Detail
The clamp is designed as a compression clamp, meaning it connects conductors firmly together by mechanical pressure. This design allows for the connection of round conductors with a diameter of 6 to 20 mm, as well as flat conductors with a cross-section dimension of 30 mm width and 3 to 4 mm thickness. The designation BSB stands for bare steel sheet, indicating the material finish. Thus, the clamp is suitable for use in concrete environments where high mechanical strength and electrical conductivity are required.
Technology Explained Simply
The compression clamp operates on the principle of mechanical compression: the conductors are inserted into the designated openings and securely clamped by the compression clamp. This ensures a permanent, electrically conductive connection without additional connection means such as screws or soldering. The construction in accordance with DIN EN 62561-1 ensures that the clamp meets the requirements for electrical conductivity, mechanical strength, and corrosion resistance. The use of bare steel sheet (BSB) provides high strength and sufficient conductivity, which are necessary for the function in the earthing system.
Compatibility and Accessories
The clamp is compatible with round conductors in the diameter range of 6 to 20 mm and flat conductors with dimensions of 30 mm × 3 mm to 4 mm. It can be used in T-, cross- and parallel arrangements, enabling flexible integration into existing or newly created earthing systems. The connection is made directly with reinforcement mesh or reinforcement steel, thereby utilizing the earthing properties of the entire concrete component.
Installation and Mounting
Installation is carried out by inserting the conductors to be connected into the respective openings of the compression clamp and then securely clamping them. The clamp is placed directly onto the reinforcement steel or reinforcement mesh, with the mechanical connection being ensured by the compression clamp. No additional tools or auxiliary means are required to create the connection. Installation takes place in concrete foundations or concrete structures, with the clamp being embedded in the concrete to ensure a permanent connection.
Advantages in Operation
The compression clamp provides a reliable, durable, and maintenance-free connection between different conductors and reinforcement steel. The construction in accordance with DIN EN 62561-1 ensures high electrical conductivity and mechanical stability, which are crucial for the function in lightning protection and earthing systems. The use of bare steel sheet ensures sufficient corrosion resistance in concrete environments. The simple installation without additional tools or connection means reduces installation time and installation effort.