Further information for DEHN 106120 DIDH 16 690 BP V2A GFK iso-distance holder Rd16 mm 690 mm
General
Diameter
16 mm
Material
Fibre-reinforced plastic (FRP)
Colour
Light grey
Material factor km
0,7
Model
with rod holder and mounting plate
Norm
DIN EN 62305-3 (VDE 0185-305-3)
Conductor support Rd
16 mm
Material of conductor holder
StSt
Length (l1)
690 mm
Insulating clearance (l2)
605 mm
Fixing
[8x] Ø5.1 / [4x] 7 x 10 / [2x] 11 x 20 mm
Permanent temperature range
-50 °C ... +100 °C
Standard
DIN EN IEC 62561-8 (VDE 0185-561-8)
UV stabilisation
The DEHN spacing holder DIDH 16 690 BP V2A GFK is a component specifically developed for lightning protection technology to ensure safe separation of air terminals within grounding systems. It is used to maintain the required separation distance according to DIN EN 62305-3 (VDE 0185-305-3), preventing unwanted electrical coupling between lightning protection conductors and other metallic conductors. The spacing holder is made of glass-fibre-reinforced plastic (GFK), providing high mechanical strength and chemical resistance. The construction includes a cylindrical spacing rod with a diameter of 16 mm and a length of 690 mm, which is UV-stabilized and finished in light grey. The material factor km is 0.7, describing the electrical conductivity of the material taking into account its physical properties.
Applications
The spacing holder is used in lightning protection systems, particularly at locations where air terminals or other metallic conductors are installed near grounding conductors. It ensures that the required distance between these conductors is maintained, minimizing the risk of overvoltages or spark discharges in the event of a lightning strike. Typical applications include buildings, industrial facilities, or outdoor installations where safe separation of metallic conductors is necessary.
Functions and Equipment in Detail
The spacing holder features a fixed rod holder that enables secure and stable guidance of the air terminal. The combination of the GFK rod and mounting elements ensures a durable and robust installation that remains stable even under external influences such as UV radiation or mechanical stress. The light grey colour is a visual characteristic but does not affect functionality.
Technology Explained Simply
The use of GFK as a material provides high insulation capability and mechanical strength. UV stabilization prevents material degradation due to sunlight exposure, extending the product’s service life. The material factor km=0.7 is a parameter used in calculating the separation distance in lightning protection systems to account for the material’s electrical properties. The fixed conductor guidance provided by the rod holder ensures the air terminal cannot move, thus precisely maintaining the required position.
Compatibility and Accessories
The spacing holder is specifically designed for air terminals and is used in conjunction with lightning protection systems.
Mounting and Installation
Installation is carried out using the integrated mounting plate, which is fixed at the desired location. The air terminal is inserted into the rod holder, ensuring exact positioning and the required separation distance.
Operational Advantages
Using this spacing holder increases the safety of the lightning protection system by minimizing the risk of electrical discharges between metallic conductors. The UV stabilization and high mechanical strength of the GFK material ensure a long service life and low maintenance requirements. The fixed conductor guidance prevents displacement and guarantees consistent maintenance of the separation distance.