| General |
| Material of air-termination rod | Al |
| Length of air-termination rod | 2500 mm |
| Material of supporting tube | GRP / Al |
| Length of supporting tube | 1955 mm |
| Transport length | 2500 mm |
| Diameter Ø outside | 50 mm |
| Length of insulating clearance | 1560 mm |
| Wall thickness | 4 mm |
| Material factor km | 0.7 |
| Permanent temperature range | -50 °C ... +100 °C |
| Type | UV-stabilised |
| Sleeve | 60 x 5 mm |
| Max. gust wind speed | 140 km/h |
| Pull-out force with a length of 500 mm | 200 N (supporting tube insulator as per 62561-8) |
| Bending force with a length of 500 mm | 200 N (supporting tube insulator as per 62561-8) |
| Standard | DIN EN IEC 62561-8 (VDE 0185-561-8) |
DEHNcon-H support tube GRP/Al for HVI light conductor with air-termination rod, for setting up separate (insulated) air-termination systems. System for maintaining the separation distance from electrically conductive parts in accordance with DIN EN 62305-3 (VDE 0185-305-3). Tube D30 mm made of glass-fiber reinforced plastic (GRP), UV-stabilized, light gray, material factor km=0.7. One-piece design, combined with air-termination rod (D22/16/10 mm, length 2500 mm) made of Al.