DEHN 103013, EAN: 4013364129818

DEHN 103013 lightning protection mast ÜFL with flange plate

Installation > Grounding Systems > Lightning protection material

DEHN 103013 lightning protection mast ÜFL with flange plate

Lieske Part No. 1893330
Mfg Part No 103013
EAN-Code 4013364129818
Manufacturer DEHN
Here only 7.932,88 EUR
9.440,13 EUR incl. VAT

Further information for DEHN 103013 lightning protection mast ÜFL with flange plate

General
Height above floor13,38 m
Maximum gust wind speed194 km/h
NormDIN EN 62561-(1+2)
FoundationPile or concrete foundation
ModelWith flange plate and plug system
Statictestable included
MaterialSt/tZn
Height above ground level (l1)13380 mm
Mast segments2
Max. gust wind speed with Concrete foundation194 km/h
Max. gust wind speed with bucket foundation143 km/h
Dimensions of flange plate400 x 400 mm
Type of flange plate4x Ø27 mm for 4x M24 (300 x 300 mm)
Dim. of on-site concrete foundation (l x w x h)1400 x 1400 x 900 mm
StandardEN 62561-(1+2)
The DEHN Tele-Blitzschutzmast type TBM 13.35M FP400 STTZN is a lightning protection mast specifically designed for use in critical and sensitive installations. It provides protection against direct lightning strikes and is particularly intended for applications such as biogas plants, photovoltaic installations on open areas, explosion protection systems (Ex systems), and ammunition storage facilities. The mast is designed for mounting on precast or concrete foundations, either using pre-fabricated precast foundations or by means of an anchor cage in a site-cast concrete foundation. The construction allows for a secure and stable installation, taking into account the respective static requirements.

Applications
This lightning protection mast is designed for use in industrial and technical installations exposed to an increased risk of direct lightning strikes. It is particularly suitable for large-area open installations such as photovoltaic open-area systems, where sufficient lightning protection coverage is required. In installations with increased explosion hazard, such as biogas plants or ammunition storage, the mast provides a safe protective measure. The application is in areas where a verified and documented lightning protection function is required.

Functions and Equipment in Detail
The mast features a gland plate, enabling quick and precise installation. The conical mast sections are equipped with a plug system, allowing modular and tool-free assembly of individual sections. The total height above floor level is 13.38 m, ensuring sufficient protection zone over the object to be protected. The design with gland plate and plug system ensures efficient installation and high mechanical stability.

Technology Explained Simply
The lightning protection mast is dimensioned according to Eurocode 1 (DIN EN 1991-1-4 + DIN EN 1991-1-4/NA) and designed for a maximum gust wind speed of 194 km/h. This ensures the mast remains stable even under extreme weather conditions. The construction is tested in accordance with DIN EN 62561-(1+2), confirming compliance with European standards for lightning protection systems. The verifiable statics are included in the delivery and enable documented and traceable static design.

Compatibility and Accessories
The mast is designed for mounting on precast or concrete foundations. The use of precast foundations as prefabricated elements or installation with an anchor cage in a site-cast concrete foundation are the intended mounting variants. The construction is designed to be compatible with the respective foundation solutions.

Installation and Mounting
Mounting is performed via the gland plate, which allows secure fastening to the foundation. The individual mast sections are assembled using the plug system, enabling tool-free installation. Installation requires adherence to the static requirements included in the delivery scope. Mounting is typically carried out by specialists familiar with the requirements for lightning protection systems.

Operational Advantages
The lightning protection mast provides reliable protection against direct lightning strikes. The modular construction with plug system allows for quick and easy installation. The tested statics and dimensioning according to Eurocode 1 ensure high mechanical stability even under extreme wind loads. Compliance with DIN EN 62561-(1+2) ensures the mast meets the required safety standards.

Protection type, operating voltage, height, wind load, standard, foundation are the central technical terms associated with this product. The height above floor level is 13.38 m. The maximum gust wind speed for which the mast is designed is 194 km/h. The standard DIN EN 62561-(1+2) is the underlying lightning protection standard. The foundation variants are precast foundation or concrete foundation with anchor cage.