Highlights:
• Simple, compact, and user-friendly multifunction device for quick and effective testing of electrical safety in installations according to DIN VDE 0100-600, DIN VDE 0105-100, etc.
• Features: continuity testing, insulation measurement, loop and network impedance measurement (Zs, Zi), FI/RCD testing
• Optional current measurement with a clamp meter providing voltage output
• Battery-powered and always ready for use
Description:
Key Strengths:
- Ground testing via loop impedance measurement
- Continuity testing with 0.2 A
- Insulation testing
- FI/RCD testing: trip time and trip current
Ergonomics:
The C.A 6131 multifunction tester offers straightforward operation and is designed for practical use:
- Foldable stand for tabletop use
- 4-point shoulder strap for hands-free operation
- Backlit display for clear visibility in low-light environments
- Precisely labeled terminals (L, N, PE, +, com) to avoid connection errors
- External probe for remote control during testing
- 3-pole test lead for direct measurements on Type-E plugs
Measurement Functions:
With the C.A 6131, the following tests can be performed:
- Voltage measurement
- Continuity testing (resistance)
- Insulation measurement
- Loop measurement (impedance)
Current measurement is possible using an external clamp meter. FI/RCD circuit breaker testing (types A and AC) is conducted in ramp or pulse mode. The device also indicates phase rotation. Test results (pass/fail) are displayed instantly.
Key Technical Specifications:
- Voltage Measurement: up to 550 V AC / 800 V DC
- Continuity Resistance: up to 200 mA
- Resistance Measurement: from 1 to 99.99 kΩ
- Insulation Measurement: Test voltage 250 V and 500 V, range up to 999 MΩ
- Loop Impedance:
- Zs (Z L-PE) without tripping: from 1 to 2000 Ω, short-circuit current Ik calculation
- High-current loops: Zs (Z L-PE) with tripping, Zi (Z L-N or Z L-L), from 0.1 to 400 Ω, Ik calculation
- FI/RCD Testing:
- Types AC & A: 30 mA, 100 mA, 300 mA, 500 mA, 650 mA
- Impulse Mode: trip time
- Ramp Mode (30 mA): trip current
- Phase Rotation Direction: 45 to 550 V; 45 to 65 Hz