Further information for Chauvin Arnoux 6528 insulation meter - P01140838
Highlights:
• Compact, robust, and digital insulation and continuity tester for insulation resistance measurements up to 11 GΩ and resistance measurements up to 420 kΩ
• 3 test voltages (250 V / 500 V / 1000 V) for a wide range of applications
• Dual-line digital display: Simultaneous display of insulation resistance and actual test voltage
• Display with dual-color Pass/Fail indication (blue/red)
• 3 test modes: Manual, continuous operation, or timer
• High safety: Automatic detection of hazardous voltages with test interruption
• Standard-compliant continuity testing with 200 mA and automatic lead compensation for improved accuracy
Description:
The C.A 6528 insulation tester is designed for maintenance and repair tasks on electrical devices such as motors and cables. With its transport case for hands-free operation, the C.A 6528 enables unrestricted on-site use. Its shock-resistant housing with a stand ensures stability and ease of use.
The device features a large LCD display with dual-line presentation, simultaneously showing the insulation resistance and actual test voltage. Backlighting ensures perfect readability in all conditions.
The C.A 6528 megohmmeter complies with international standards like IEC 60364, NF C 15-100, and VDE 100, making it suitable for insulation, resistance, and continuity testing. Automatic voltage monitoring prevents insulation tests under hazardous voltage conditions (> 30 V). If measured values exceed the preset thresholds, the display color changes from blue to red.
Technical Data:
• Voltage: 0 to 700 VAC/DC
• Insulation testing: Up to 11 GΩ
• Continuity testing: 0.02 Ω to 40 Ω
• Resistance measurement: 1 Ω to 420 kΩ
• Automatic detection of applied voltages
• Standards: IEC 61557-1-2-4-10
• Electrical safety: IEC 61010-1, 61010-2-030, 61010-2-034 – 600 V CAT IV
• Protection rating: IP 40
• Dimensions: Compact and lightweight for easy handling