Highlights:
- Large clamp current transformer for measuring the smallest leakage currents in power circuits
- Enclosure Ø: 115 mm
- Input: Measurement range 0.5 mA…4 A | 0.5 A…400 A
- Output signal: Alternating voltage
- Transformation ratio: 1 mA/1 mV | 1 A/1 mV, Typical accuracy: ≤ 0.5% | 0.35%
- Output: via cable and plug (Ø 4 mm, insulated)
Description:
The B102 clamp meter is designed specifically for detecting and pinpointing the smallest leakage currents flowing to earth. It facilitates rapid fault diagnosis without interrupting system operations.
With a measurement range starting at 500 µA, the clamp captures both differential currents and currents up to 400 A. Two measurement ranges (1 mV/mA and 1 mV/A) offer flexibility, while the large jaw opening of 110 mm simplifies measurements on thick conductors.
The B102 is suitable for single-phase and multi-phase systems, regardless of whether currents are in-phase, phase-shifted, symmetrical, or asymmetrical. Using an optional adapter for an artificial neutral conductor, it can accurately measure leakage currents in 3-phase power systems.
Technical Data:
- Measurement range: 0.5 mA…4 A | 0.5 A…400 A
- Output signal: Alternating voltage
- Transformation ratio: 1 mA/1 mV | 1 A/1 mV
- Typical accuracy: ≤ 0.5% (small currents) | ≤ 0.35% (large currents)
- Jaw opening: 110 mm
- Enclosure diameter: 115 mm
- Application: Leakage current measurement and differential current detection
- Compatibility: Single-phase and multi-phase systems
Included Items:
- Clamp current transformer model B102
- User manual