General
Operating voltage1 kV
Cable cross-section4x25 or 5x16 mm²
Inner diameter45 mm
Epoxy resin typePUR, hydrolysis resistant, EG
Compatibilitycables with PVC, PE, VPE, EPR insulation
Connection technologyScrew or push-in connector
Test standardDIN VDE 278, Part 2 and Part 3
The Cellpack M2 is a casting resin connection sleeve for the electrical connection of plastic cables with insulation made of PVC, PE, VPE, and EPR, for example, with cable types such as N(A)YY, NYM, or TT. It serves as a permanent and weather-resistant connection unit in the field of cable installation, particularly for connecting copper and aluminium conductors using crimp or screw connectors. The sleeve is designed for use indoors, outdoors, in soil, in water, and in cable ducts, providing a reliable electrical and mechanical connection.

Applications

The M2 casting resin connection sleeve is universally applicable in electrical installation, particularly in areas requiring high mechanical load capacity and weather resistance. It is suitable for installations in buildings, industrial facilities, outdoor environments, and underground or water-bearing environments. The sleeve is used with cables having a maximum cross-section of 4x25 mm² or 5x16 mm², ensuring secure sealing and mechanical stabilisation of the cable connection.

Functions and Equipment in Detail

The sleeve is equipped with hydrolysis-resistant PUR casting resin EG, which ensures permanent sealing of the connection against moisture, water, and other environmental influences. The casting resin provides an electrically insulating and mechanically stable connection that remains intact even under stress from temperature fluctuations or mechanical strain. The sleeve is designed for cable diameters from a minimum of 7 mm to a maximum of 33 mm, with a length of 267 mm and a maximum internal diameter of 45 mm.

Technology Explained Simply

The PUR casting resin EG is poured into the sleeve, where it cures to form a solid, waterproof connection between the cables. The hydrolysis resistance of the resin means that it does not degrade or lose its properties even under prolonged moisture exposure. The sleeve itself is designed to mechanically fix the cables while simultaneously providing electrical insulation between the conductors. The use of crimp or screw connectors allows flexible adaptation to various cable types and conductor materials.

Compatibility and Accessories

The M2 sleeve is compatible with cables using PVC, PE, VPE, or EPR as insulation material. Available accessories include the casting resin pack EG 370 with 370 ml of resin and the UNIVERSALCLEANER121 spray can cleaner 400 ml. The resin pack is used to fill the sleeve, while the cleaner is used to prepare the cable and sleeve surfaces before pouring. The sleeve is designed for use in systems up to 1 kV.

Installation and Mounting

Installation involves inserting the cables into the sleeve, connecting the conductors using crimp or screw connectors, and then pouring in the PUR resin EG. The sleeve can be mounted both horizontally and vertically; for vertical mounting, an optional pouring angle (e.g., for M3) is recommended to support resin flow. Curing of the resin follows the manufacturer’s instructions, after which the sleeve forms a permanent, waterproof connection.

Operational Advantages

The Cellpack M2 provides a reliable, permanent, and weather-resistant cable connection that remains stable even under challenging environmental conditions such as moisture, soil, or water exposure. The use of hydrolysis-resistant PUR resin ensures a long service life for the connection. Its universal applicability for various cable types and conductor materials, along with compatibility with crimp and screw connectors, increases installation flexibility. The sleeve is tested according to DIN VDE 278, Part 2 and Part 3, confirming compliance with relevant standards for electrical connections.
This is an offer of: