Further information for Brandmeldekabel BMK Y(ST)Y 4X2X0,8 R - Fire alarm cable 4x2x0 8 drum structure JY (ST) 250 red
			
			Fire alarm cable JY (St) Y. .. Lg 0.8 mm, red according to VDE 0815
  Application:
Preferably in the stations and private branch within buildings, but also outdoor zurfesten laying on buildings. These cables are specially designed for fire alarm systems.
  Building:
 Conductor: copper conductor, solid
  blank
 0.8 mm diameter
  Insulation: PVC
Marking: according to VDE 0815 stranding: cores to pairs pairs in layers of static shield: plastic laminated metal foil with drain wire
  Film
Outer sheath: PVC red with imprint '''' Fire Alarm Cable
  Specifications:
  Rated voltage: 300 V
  Test voltage: 800 V
Loop resistance: 73.2 / km Current Rating: 5.1 A
  Operating capacity: 100 nF / km
 Insulation resistance: 100 km Mx
  Capacitive
  Couplings: K1 (800 Hz, 100 m) 300pF
 Line attenuation: about 1.1 dB / km (800 Hz)
  Temperature range: - 5 ° C - + 50 ° C
  (During installation)
  - 30 ° C - + 70 ° C
  (After installation)
  Operating temperature: + 70 ° C (max.)
  Bending radius: 7,5 x cable diameter
  2.5 x cable diameter
  for single bending without
  Train
  Flame resistance according to VDE 0472 T. 804
  Category B (= IEC 332-1)
  Diameter in mm: 4 x 2 x 0.8
  Outer diameter approx: 9.0
  Copper content (kg / m%): 4.1
  Weight (kg / m%): 9.5
 Type: DT Y (ST) Y 4X2X0, 8 RT item: 1 MTR