Further information for böhm Kabel YSLYCY-JZBLACK5x0,75 control cable 5x0,75 mm² black
General
Nominal voltage
0,6/1 kV
Test voltage
4000 V
Insulation resistance
20 MΩ·km
Current carrying capacity
According to DIN VDE 0298 Part 4
Minimum bending radius
20 x conductor Ø
Temperature range in motion
-5 °C
Temperature range for fixed installation
-40 °C
Radiation resistance
80 Mrad
Coupling resistance
250 Ω/km
Shielding cover
85 %
Core insulation
T12 in accordance with DIN VDE 0281 Part 1
Outer sheath
TM2 in accordance with DIN VDE 0281 Part 1
Type of test
B in accordance with VDE 0472 Part 804
Copper stranded wire
Kl.5 in accordance with DIN VDE 0295
Protective conductor
yellow-green in outdoor installation
Digit coding
white on black in accordance with DIN VDE 0293
Chemical resistance
oil-resistant
UV resistant
Self-extinguishing
Flame retardant
The YSLYCY-JZ 5x0.75 0.6/1kV BLACK is a flexible PVC control cable from the manufacturer böhm Kabel, designed for use in industrial applications such as machine tools, conveyor and transfer belts, production lines, plant engineering, and climate technology, particularly in steelworks and rolling mills. The cable is suitable for flexible installation under moderate mechanical stress, provided there is no tensile load and no forced movement guidance. It can be permanently installed in dry, damp, and wet rooms as well as outdoors, but not directly in soil or water. The black special PVC outer sheath is UV-resistant and offers high chemical resistance, especially against oil. Due to the extended rated voltage range and UV resistance, the cable is particularly used in southern European, Arab, Asian, and eastern countries.
Applications
This control cable is intended for measurement, control, and signaling purposes in industrial environments. It is used in installations with moving parts where a flexible yet stable connection is required. Installation takes place indoors and outdoors, but the cable must not be placed in direct contact with soil or water. The application is in environments with moderate mechanical stress, where the cable is not under tension and no forced movement guidance is applied.
Functions and Features in Detail
The cable features bare, fine-stranded Cu conductors according to DIN VDE 0295 Class 5 or IEC 60228 Class 5. The conductors are insulated with special PVC, type T12 according to DIN VDE 0281 Part 1. The black conductors are marked with a continuous white digit print according to DIN VDE 0293, enabling clear identification of individual conductors even when stripped short. Base lines prevent misreading of digits. The green-yellow protective conductor is positioned in the outer layer starting from three conductors. The conductors are stranded in layers with optimal lay lengths to ensure even distribution and mechanical stability.
Technology Explained Simply
A key component of the cable is the shielding braid made of tinned copper wires with a coverage of approximately 85%. This ensures high shielding density and enables interference-free signal and pulse transmission. The EMC properties (Electromagnetic Compatibility) can be optimized by bilateral and extensive full-contact grounding of the copper braid. The special PVC outer sheath, type TM2 according to DIN VDE 0281 Part 1, is self-extinguishing and flame-retardant (test type B according to VDE 0472 Part 804 and IEC 60332-1), increasing safety in fire hazards. The cable is largely oil-resistant and radiation-resistant up to 80 Mrad (80x10^6 cJ/kg), making it suitable for environments with high radiation exposure.
Compatibility and Accessories
The cable is designed for use in industrial control and regulation circuits. It is compatible with standard connectors and terminals designed for flexible PVC cables. The use of appropriate shielding and grounding terminals for secure contact of the copper braid is recommended to ensure EMC performance. The cable can be used in combination with other control cables and switching devices that meet the same electrical and mechanical requirements.
Installation and Mounting
Installation is done by permanent fixing in suitable conduits without tensile stress. The minimum bending radius is 20 times the cable outer diameter. The cable must not be laid in direct contact with soil or water. Connections between conductors are made using suitable connectors or terminals. The shielding should be contacted bilaterally and extensively to optimize electromagnetic compatibility.
Operational Advantages
The YSLYCY-JZ 5x0.75 0.6/1kV BLACK offers high mechanical stability with flexible installation, reliable signal transmission due to high shielding density, and high chemical and UV resistance. The self-extinguishing and flame-retardant design increases operational safety. The clear digit coding of the conductors simplifies installation and maintenance. The cable is designed for use in industrial environments with high demands on reliability and safety.
Temperature Range
The cable can be operated in moving applications within a temperature range of -5 °C to +70 °C. For fixed installation, the temperature range is -40 °C to +80 °C. Current loading is according to DIN VDE 0298 Part 4. The test voltage is 4000 V, and the insulation resistance is at least 20 MΩ·km. The coupling resistance is limited to a maximum of 250 Ω/km, ensuring signal quality.
Protection Class and Resistance
The cable is suitable for outdoor use, as the outer sheath is UV-resistant. The chemical resistance against oil and the radiation-resistant design (up to 80 Mrad) make it suitable for demanding industrial environments. The self-extinguishing and flame-retardant property (test type B) increases safety in fire hazards.