| General |
| Nominal voltage | 0,6/1 kV |
| Test voltage | 3 kV |
| Insulation resistance | 20 MΩ·km |
| Installation temperature range | -20 to +80 °C |
| Temperature range after installation | -40 to +80 °C |
| Operation temperature | +90 °C |
| Bending radius | 5 x cable diameter min. with free installation |
| Flame retardancy | VDE 0472 T. 804, test type B (IEC 332-1) |
| Oil resistance | VDE 0472 T. 803, test type A |
| Conductor | tinned copper stranded wire, fine-stranded class 5 |
| Wire insulation | Rubber compound according to VDE 0207 T. 20 |
| Conductor marking | according to VDE 0293-308 |
| Outer sheath | Rubber compound according to VDE 0207 T. 21 |
| Sheath colour | Yellow |
The NSSHÖU-J 3X2,5 from böhm Kabel is a heavy-duty rubber-sheathed cable designed for extremely high mechanical stresses. It is particularly suitable for use in underground mining, open-pit mining, construction sites, and industrial applications. The cable is intended for use in dry and damp rooms as well as outdoors and can also be used for fixed installation, with specific application conditions to be defined on a case-by-case basis. The yellow outer sheath color identifies the cable as a special cable for demanding environments.
Applications
The cable is designed for applications involving high mechanical loads, such as tension, pressure, bending, or abrasion. It is frequently used in the mining industry, civil engineering, construction sites, and production facilities where robust and long-lasting cable systems are required. Outdoor use is possible, as the cable is resistant to moisture and weather influences. Fixed installation is also permitted, with specific on-site conditions to be considered.
Functions and Equipment in Detail
The cable consists of tinned copper conductors of fine-strand class 5, ensuring high flexibility and durability. The conductors are insulated with a rubber compound according to VDE 0207 T. 20 and marked in accordance with VDE 0293-308, enabling clear identification of individual conductors. The conductors are stranded with optimal lay lengths to ensure even distribution of mechanical stress. The outer sheath is made of a rubber compound according to VDE 0207 T. 21 and is colored yellow, identifying the cable as a special cable.
Technology Explained Simply
The rated voltage is 0.6/1 kV, making the cable suitable for a wide range of industrial applications. The test voltage of 3 kV ensures electrical strength. The insulation resistance of 20 MΩ·km at 20 °C guarantees high electrical insulation. The temperature ranges are -20 °C to +80 °C during installation and -40 °C to +80 °C after installation, with a maximum operating temperature of +90 °C. The minimum bending radius is 5 times the cable diameter for free installation, supporting flexibility during installation. The cable meets fire behavior requirements according to VDE 0472 T. 804, test type B (equivalent to IEC 332-1), and is oil-resistant according to VDE 0472 T. 803, test type A. Flame retardancy corresponds to VDE 0482-332-1-2 (IEC 60332-1), enhancing safety in fire hazard situations.
Compatibility and Accessories
The cable is designed for use in industrial and mining environments and can be combined with appropriate connectors, terminals, and protection systems designed for high mechanical loads. The yellow color serves as a visual identifier for special cables and supports identification during use.
Installation and Mounting
Installation for free routing requires a minimum bending radius of 5 times the cable diameter. Routing is possible in dry and damp rooms as well as outdoors. The temperature conditions during installation range from -20 °C to +80 °C, and after installation from -40 °C to +80 °C. The maximum operating temperature is +90 °C. The cable is suitable for fixed installation, with specific application conditions to be defined on a case-by-case basis.
Operational Advantages
The NSSHÖU-J 3X2,5 offers high mechanical strength, resistance to oil and moisture, and excellent electrical insulation. The high flexibility of the fine-strand copper conductors of class 5 enables long service life even under frequent bending and tension loads. The flame-retardant and oil-resistant design increases safety in hazardous environments. The yellow color facilitates identification and marking during use.
Protection Rating
The cable is not classified as an IP protection rating but meets the requirements for mechanical strength, oil resistance, and flame retardancy according to the specified standards. Outdoor use is possible, as the rubber compound of the outer sheath is resistant to weather influences.
Operating Voltage
The rated voltage of 0.6/1 kV makes the cable suitable for a wide range of industrial applications, particularly in environments with high mechanical loads.
Technology
The use of tinned copper conductors of class 5 and rubber compounds according to VDE 0207 T. 20 and T. 21 represents a proven technology for robust and long-lasting cable systems.
Standard
The cable meets the requirements of VDE 0207 T. 20 and T. 21, VDE 0293-308, VDE 0472 T. 804, VDE 0472 T. 803, and VDE 0482-332-1-2 (IEC 60332-1), ensuring quality and safety.