| General |
| Degree of protection | halogen-free |
| Operating voltage | 300/500 V |
| Maximum permissible operating voltage AC and three-phase | 330/550 V |
| Maximum permissible operating voltage DC | 825 V |
| Short-circuit temperature | 250 °C |
| Conductor resistance | according to DIN/VDE |
| Test voltage | 50 Hz, 5 min. |
| Features | flame retardant |
| Application | Wiring of luminaires, devices, control panels, distributors |
| Installation | in conduits, on, in and under plaster, in closed installation channels |
| Utilization | internal wiring of devices, control panels, distributors |
| Norm | DIN VDE Part 3 |
| Conductor | Fine-stranded bare |
| Insulation | halogen-free cross-linked polymer blend |
The H07Z-K 2.5 WS is a halogen-free single-core cable from the manufacturer böhm Kabel, designed for use in dry rooms and in installations with high personnel or asset concentration. It is used for wiring of lighting fixtures, devices, control panels and distributors, as well as for installation in buildings and vehicles. The cable is suitable for installation in conduits, on, in and under plaster, as well as in closed installation ducts. It may also be used for internal wiring of devices, control panels and distributors, and for protected installation in and on lighting fixtures. General requirements are based on DIN VDE Part 3.
Applications
This cable is intended for use indoors, particularly in buildings with increased safety requirements, such as hospitals, schools, office buildings or public transport vehicles. It is suitable for electrical connections of lighting installations, electrical devices and control panels. Installation takes place in closed installation systems, with the cable being run in conduits or ducts. Use in damp or wet areas is not permitted.
Functions and Features in Detail
The H07Z-K 2.5 WS features a fine-stranded, bare conductor, providing high flexibility and mechanical durability. The insulation consists of a halogen-free, cross-linked polymer blend, making the cable flame-retardant and producing only low smoke density when exposed to fire. These properties are especially important in areas with high visitor traffic, to minimize smoke development and flame spread. Thus, the cable is suitable for applications where personnel safety is paramount.
Technical Explanation
The cable is rated for nominal voltages of 300/500 V and 450/750 V, with maximum permissible operating voltages in alternating and three-phase systems at 330/550 V and 495/825 V respectively. In direct current systems, the maximum permissible operating voltage is 825 V. The maximum operating temperature of the conductor is 90 °C, while the short-circuit temperature can reach 250 °C. The conductor resistance complies with DIN/VDE standards. The cable is designed for operation at ambient temperatures within the technical specifications.
Compatibility and Accessories
The H07Z-K 2.5 WS is designed for use in standard installation systems and can be combined with common installation conduits, ducts and distributors. It is suitable for use in electrical installations executed according to DIN VDE Part 3. The cable is not intended for use in explosive environments or outdoors. Use with special protection systems or in special environments requires separate evaluation of requirements.
Installation and Mounting
Installation takes place in closed installation systems, with the cable being run in conduits or ducts. The cable is installed on, in and under plaster, but must not be used in damp or wet areas. It is suitable for internal wiring of devices, control panels and distributors. Mounting does not require special tools, but installation must comply with applicable standards and regulations.
Operational Advantages
The H07Z-K 2.5 WS offers high safety due to its flame-retardant and halogen-free properties. The low smoke density during fire exposure improves visibility and evacuation possibilities. The cable is flexible and mechanically durable, facilitating installation. Its use in buildings with high personnel or asset concentration is particularly beneficial due to its safety characteristics. The cable is suitable for use in vehicles, where passenger safety is a priority.