| General |
| Nominal voltage | 0,6/1 kV |
| Test voltage | 3 kV |
| Insulation resistance | 20 MΩ·km |
| Installation temperature range | -20 to +80 °C |
| Temperature range after installation | -40 to +80 °C |
| Operation temperature | +90 °C |
| Bending radius | 5 x cable diameter |
| Flame retardancy | VDE 0472 T. 804, test type B |
| Oil resistance | VDE 0472 T. 803, test type A |
| Conductor | tinned copper stranded wire, class 5 |
| Wire insulation | Rubber compound according to VDE 0207 T. 20 |
| Outer sheath | Rubber compound according to VDE 0207 T. 21 |
| Sheath colour | Yellow |
| Conductor marking | according to VDE 0293-308 |
| Number of cores | 5 |
| Core cross section | 10,0 mm² |
The rubber hose cable NSSHÖU-J 5 X 10,0 from böhm Kabel is a robust, multi-core cable designed for applications with very high mechanical loads. It is particularly suitable for use in underground mining, open-pit mining, construction sites, and industrial environments. The cable can be used in both dry and damp rooms as well as outdoors and is also suitable for fixed installation, although the specific application conditions must be checked individually. The outer sheath is yellow, enabling easy visual identification.
Applications
This cable is designed for environments where high mechanical stresses such as tension, pressure, bending, or abrasion occur. It is frequently used in heavy industry, construction, and mining, where high mechanical strength and durability are required. Outdoor use is possible, as the cable is also resistant to moisture and weather influences. Fixed installation is also permitted, although the exact application must be defined on a case-by-case basis.
Functions and Equipment in Detail
The cable consists of five conductors, each with a cross-section of 10.0 mm². Each conductor is insulated with a rubber compound according to VDE 0207 T. 20, ensuring high electrical insulation and mechanical stability. The conductors are stranded with optimal lay lengths, enhancing flexibility and mechanical strength. The conductors are made of tinned copper wire, class 5, i.e., fine-stranded, which provides high bending strength and flexibility. The conductor identification follows VDE 0293-308, ensuring unambiguous identification of individual conductors.
Technology Explained Simply
The rated voltage is 0.6/1 kV, meaning the cable is designed for operating voltages up to 1 kV AC. The test voltage of 3 kV is used for safety testing and ensures the insulation remains stable under increased voltage. The insulation resistance of 20 MΩ·km at 20 °C indicates high electrical insulation properties. The operating temperature can reach up to +90 °C, with installation permitted at temperatures from -20 °C to +80 °C. After installation, the cable is suitable for temperatures from -40 °C to +80 °C. The minimum bending radius is 5 times the cable diameter for free installation, enabling flexible handling.
Compatibility and Accessories
The cable is designed for use in industrial and construction applications where high mechanical loads and environmental conditions prevail. It can be combined with appropriate connectors, cable lugs, and other connection elements suitable for the specific application. The use of accessories depends on the specific installation and project requirements.
Installation and Mounting
Installation is typically done by laying the cable in open runs or in ducts, ensuring the minimum bending radius of 5 times the cable diameter is maintained. Installation must occur at temperatures between -20 °C and +80 °C. After installation, the cable is designed for operating temperatures up to +90 °C. No special tools are required for installation, although adherence to technical specifications is essential to avoid damage.
Operational Advantages
The cable is characterised by high mechanical strength, flexibility, and durability. The rubber compound of the outer sheath, according to VDE 0207 T. 21, provides high resistance to oil, moisture, and mechanical stress. Flame retardancy according to VDE 0482-332-1-2 (IEC 60332-1) and fire behaviour according to VDE 0472 T. 804 (test method B) enhance operational safety. Oil resistance according to VDE 0472 T. 803 (test method A) makes the cable suitable for environments with oil or grease contact.
Protection Class and Environmental Resistance
The cable is suitable for outdoor use and in damp rooms, as it is resistant to moisture and weather influences. The mechanical strength and flexibility of the fine-stranded copper wire ensure a long service life even under harsh operating conditions. The yellow outer sheath colour facilitates visual identification during use.
Technical Standards and Norms
The cable complies with VDE 0207 T. 20 and T. 21 for insulation and outer sheath. Conductor identification follows VDE 0293-308. Flame retardancy is tested according to VDE 0482-332-1-2 (IEC 60332-1), and fire behaviour conforms to VDE 0472 T. 804 (test method B). Oil resistance is verified according to VDE 0472 T. 803 (test method A). These standards guarantee the safety and reliability of the cable in industrial applications.