| General |
| Nominal voltage | 300/500 V |
| Maximum permissible operating voltage for AC and three-phase systems | 330/550 V |
| Maximum permissible operating voltage for DC systems | 825 V |
| Operating temperature at conductor | 90 °C |
| Short-circuit temperature | 250 °C |
| Conductor | Fine-stranded bare |
| Insulation | halogen-free cross-linked polymer blend |
| Features | flame retardant, halogen-free, minimal smoke density |
The H05Z-K 0.75 RT is a halogen-free single-core cable from the manufacturer böhm Kabel, designed for use in dry rooms. It is used for wiring of luminaires, devices, control panels and distributors, particularly in buildings with high personnel or asset concentration, as well as in vehicles. The cable is also suitable for installation in conduits on, in and under plaster, as well as in closed installation channels. It may be used for internal wiring of devices, control panels and distributors, as well as for protected installation in and on luminaires. General requirements are based on DIN VDE 0298 Part 3. The permissible operating temperature at the conductor is 90 °C.
Applications
This cable is intended for use indoors, particularly in areas with increased safety requirements. It is suitable for wiring in buildings such as office complexes, hospitals, schools or public transport vehicles, where minimizing smoke and gas emission during a fire is important. Installation takes place in closed systems such as conduits or channels, and is not intended for open outdoor installation.
Functions and Features in Detail
The H05Z-K 0.75 RT features a fine-stranded, bare conductor, providing high flexibility and easy handling. The insulation consists of a halogen-free, cross-linked polymer blend, making the cable flame-retardant and releasing only small amounts of smoke gases in case of fire. These properties are particularly important in areas with high visitor traffic or in installations where smoke development could pose a hazard.
Technology Explained Simply
The cable is rated for nominal voltages of 300/500 V and 450/750 V. The maximum operating temperature at the conductor is 90 °C, and the short-circuit temperature is 250 °C. These values ensure safe and reliable operation under normal conditions.
Compatibility and Accessories
The cable is suitable for use in standard installation systems, particularly in closed conduits and channels. It can be combined with other halogen-free cables to ensure a consistent fire protection concept. Use in vehicles requires coordination with respective safety regulations.
Installation and Mounting
Installation takes place in closed systems such as conduits or channels, which protect against mechanical stress and environmental influences. The cable is flexible and easy to route, with connection techniques (e.g. terminals, lampholder terminals) matching the specific requirements. Installation is carried out in dry rooms, ensuring that ambient temperature does not exceed the cable’s operating temperature.
Operational Advantages
The halogen-free composition of the insulation reduces the formation of toxic gases in case of fire, increasing building safety. The flame-retardant property slows fire spread, and the low smoke density improves visibility and evacuation possibilities. The high flexibility of the fine-stranded conductor facilitates installation, especially in complex wiring systems.
Protection Rating and Environmental Conditions
The cable is intended for use in dry indoor environments. It is not suitable for outdoor use or in damp environments, as no specific protection rating (e.g. IP) is specified. Installation is carried out in closed systems that protect against moisture and mechanical stress.