| General |
| Degree of protection | Optical isolation 2000 VAC |
| Operating voltage | 10–30 VDC |
| Power consumption | 100 mA |
| Data rate | 2400 to 19.2 kbps |
| Maximum range | 1219,2 m |
| Operation temperature | -40 to +80 °C |
| Air humidity | up to 95 % non-condensing |
| Clamping time | 1 psec |
| Peak power | 500 W |
| Connections | 2x 6-pole terminal blocks, 1x DB9 F (DCE) |
| Status indicators | 3 LEDs (RS-485 transmit, RS-485 receive, power) |
The
media converter from BlackBox, type ICD100A, is designed for converting and optically isolating
RS-232 signals into
RS-422 or
RS-485 signals. It enables the connection of devices with different serial interfaces and protects against
ground loops and
overvoltages through galvanic isolation of data and ground lines. The conversion is achieved via
optical isolation with a galvanic isolation of 2000 VAC, ensuring signal integrity in industrial environments with high interference. The converter is designed for use in
industrial plants,
automation systems, and
data communication networks, where reliable serial data transmission over long distances is required.
Applications
The converter is suitable for applications where RS-232 devices need to be connected to RS-485 or RS-422 networks. Typical use cases include integrating
sensors,
control devices,
communication modules, or
data loggers into existing industrial communication infrastructures. The maximum transmission distance is 1219.2 meters, making it suitable for decentralized installations and distributed devices. The operating temperature ranges from -40 °C to +80 °C, enabling use in extreme environments such as outdoor installations or production halls with high heat generation. Humidity can reach up to 95 %, provided no condensation occurs.
Functions and Features in Detail
The converter supports
RS-232 in half- or full-duplex operation and converts this into
RS-422 in full-duplex mode or into
RS-485 in 2-wire half-duplex or 4-wire full-duplex mode. The data transmission rate is selectable via a switch and ranges from 2400 bps to 19.2 kbps. Additional speeds between 1200 bps and 115.2 kbps are available, depending on the configuration. The
optical isolation protects connected devices from voltage spikes and potential differences caused by different grounding points. The
overvoltage protection is implemented using a bidirectional avalanche breakdown device with a clamping voltage of 7.5 V, featuring a maximum power dissipation of 500 W and a clamping time of 1 psec.
Technology Explained Simply
The
optical isolation provides galvanic separation of electrical signals between transmitter and receiver, preventing disturbances caused by ground loops or voltage spikes. Data is transmitted via light pulses and converted back into electrical signals at the receiver end. This increases interference immunity and enables secure communication over long distances. The
RS-485 interface is designed for serial communication in industrial networks, offering greater range and better interference resistance than RS-232. The
RS-422 interface enables full-duplex communication, allowing simultaneous transmission and reception. The
DIN rail mounting simplifies installation in enclosures and allows compact placement.
Compatibility and Accessories
The converter is compatible with an optional
DIN rail power supply PSD100, which can power up to six converters with 12 VDC. This enables centralized power supply for multiple devices in an enclosure. Power supply is provided via a voltage of 10 to 30 VDC at a current consumption of 100 mA. Connections consist of two 6-pin terminal blocks for the RS-485/RS-422 interface and a DB9 connector (DCE) for the RS-232 interface. Status indicators are provided by three LEDs: one for the RS-485 transmit line, one for the RS-485 receive line, and one for power supply.
Mounting and Installation
The converter is mounted on a DIN rail, enabling quick and secure installation in standard enclosures. Connections are made via terminal blocks and a DB9 connector, allowing wiring with standard cables. Data rate configuration is done via a switch on the device. Power supply is provided by an external DC source in the range of 10 to 30 VDC. Mounting requires no special tools, as it is secured via the DIN rail.
Operational Advantages
The
optical isolation and
overvoltage protection increase communication reliability and protect connected devices. The
high transmission range of up to 1219.2 meters allows connecting devices over long distances. The
wide temperature and humidity resistance makes the converter suitable for use in harsh environments. The
DIN rail mounting and
simple configuration facilitate integration into existing systems. The
LED indicators enable quick diagnosis of operational status.