Further information for Benning 044067 CM 11 current clamp TRUE RMS 0.1 mA–20 A AC
General
Measurement method
True RMS
Indication
4-digit illuminated
DC measurement range
0,1 mA - 10 A
AC measurement range
0,1 mA - 20 A
Voltage measurement range
0,01 V - 600 V
Resistance measurement range
0.1 Ohm - 600 kOhm
Continuity test
Acoustic, 100 Ohm
Pliers opening
23 mm
Safety category
CAT IV 300 V, CAT III 600 V
Battery
2 x 1.5 V Micro/AAA/LR03
Scope of delivery
Case, 2 x 1.5 V Micro/AAA/LR03 battery, test leads
Automatic switch off
after 15 min, deactivatable
Measured value memory
HOLD
Min/max value memory
MIN/MAX
Automatic range selection
Battery undervoltage indicator
ZERO function
The Benning CM 11 is a clamp meter multimeter with True RMS measurement method, specifically designed for electricians, service technicians, and maintenance personnel in the electrical trade as well as in industry. It enables precise measurements of alternating and direct current, voltage, resistance, and continuity testing. The 4-digit illuminated LCD display with 6,000-point resolution ensures clear and easy-to-read display of measurement values, even in poor lighting conditions. The clamp is compact and features a clamp opening of 23 mm, which facilitates measurement on tight or hard-to-reach conductors.
Applications
This device is versatile and suitable for troubleshooting in electrical installations, machines, equipment, automotive technology, control systems, and fire and intrusion alarm systems. It is particularly suitable for resting current measurement on automotive batteries to detect slow discharges, as well as for measuring 4 mA to 20 mA process signals without interrupting the current loop. The high resolution of 0.1 mA enables precise measurements even at very low currents, which is important for diagnostics in safety systems.
Functions and Equipment in Detail
The Benning CM 11 offers automatic and manual range selection, allowing the user to choose between both modes as needed. The automatic power-off (APO) occurs after 15 minutes but can be deactivated. A low battery indicator alerts the user in time about a weak battery. The functions measurement hold (HOLD), minimum and maximum value memory (MIN/MAX), and ZERO function support accurate documentation and analysis of measurement results. The audible continuity test at a resistance value of 100 Ohm facilitates testing of conductors and contacts.
Technology Explained Simply
The device operates using the True RMS method, which delivers accurate RMS values even for non-sinusoidal alternating currents. This is particularly important in modern electronic devices, which often produce distorted current waveforms. The direct current measurement ranges are from 0.1 mA to 10 A, with direct ranges at 300.0 mA, 3.000 A, and 10.0 A. For alternating current, the ranges are from 0.1 mA to 20 A, with direct settings at 300.0 mA, 3.000 A, and 20.0 A. Voltage measurement is performed in the range of 0.01 V to 600 V, and the resistance measurement range extends from 0.1 Ohm to 600 kOhm and is directly selectable.
Compatibility and Accessories
The device is designed for use in electrical installations according to safety categories CAT IV 300 V and CAT III 600 V, making it suitable for measurements in distribution systems and at consumers. It is supplied with a case, 2 x 1.5 V Micro/AAA/LR03 batteries, and test leads. These components are included in the delivery scope and support practical use.
Mounting and Installation
The clamp is simply placed around the conductor to be measured, with the 23 mm clamp opening enabling measurement on conductors with a diameter up to 23 mm. The test leads are connected to the corresponding terminals on the device. Operation is performed via buttons on the device, which activate the various measurement functions and settings.
Advantages in Operation
The combination of True RMS measurement, high resolution, versatile measurement functions, and compact design makes the Benning CM 11 a reliable tool for professional users. The integrated memory functions and audible continuity test increase efficiency during troubleshooting. The safety categories CAT IV 300 V and CAT III 600 V ensure safe use in various application areas.